A Method for Calculating the Growth Rate of Resistive Current and Fault Diagnosis of MOA Based on Synthetic Vector
ID:170
Submission ID:176 View Protection:ATTENDEE
Updated Time:2023-11-20 13:53:25 Hits:181
Poster Presentation
Abstract
At present, metal zinc oxide arresters are used for station-type arresters with voltage levels of 110 kV and above. The stability of the arrester valve plate mainly depends on the monitoring of resistive current. Resistive current is sensitive to the initial aging, moisture, and other reactions of the valve plate. The interference of phase capacitance is the most important factor to measure the resistive current of arrester. In order to solve the problem of low proportion of resistance current component in leakage current and difficulty in measurement in traditional MOA detection methods, this paper synthesizes the vector of the total leakage current of the three phases, and indirectly obtains the growth rate of the resistive current amplitude through the variation of the synthesized vector phase angle. The experimental results show that this method can effectively remove the influence of inter phase coupling capacitance and has greater stability to ensure the accuracy of resistive current calculation, thus truly reflecting the operating status of the lightning arrester.
Keywords
MOA, Resistive current, Synthetic vector, Phase coupling capacitance, Leakage current.
Submission Author
Gaoming Wang
Nari Technology Development Limited Company
Comment submit